Electric strike vs maglock: how do I wire the lock relay on a Mercury LP1502 (fail-safe vs fail-secure)
On a Mercury LP1502 an electric strike that unlocks when powered goes on the relay's Normally Open (NO) and Common (C) poles, so the relay delivers power to unlock. A maglock, which unlocks when power is removed, goes on the Normally Closed (NC) and Common poles, so the relay momentarily removes power. Put a protection diode (1N4002 typical for 12 or 24 V DC) across the lock to stop feedback from damaging the relay, and check local building codes for egress.
Steps
From: Mercury LP1502 Controller Installation a install guide, pp. 4, 15
- Know what the relays areThe LP1502 has four Form-C dry relays for door locks or alarm signaling. Each has a Common pole (C), a Normally Open pole (NO) and a Normally Closed pole (NC). They switch your lock power supply; they don't supply power.
- Strike that unlocks with power (fail-secure):Wire the lock supply through C and NO. The relay closes on a valid read and delivers power to the strike.
- Maglock (fail-safe):Wire the lock supply through C and NC. The magnet holds while powered, and the relay momentarily removes power to unlock the door.
- Add a diode across the lockLock coils feed back into the relay and cause damage and premature failure. Choose a diode rated 1x the strike current and 4x the strike voltage; for a 12 V DC or 24 V DC strike a 1N4002 (100V/1A) is typical.
- Mount the protection close to the lockOn the MR52-S3B Mercury calls for the protection circuit within 12 inches (30 cm) of the load; it loses effectiveness farther away.Source: HID Mercury MR52-S3B Reader Interface In install guide · p. 10
- Size the wireUse wire of sufficient gauge for the lock current to avoid voltage loss at the door.
- Check egressMercury tells you to check local building codes for proper egress door installation before you decide between a strike and a maglock.
Specs & limits
From: Mercury LP1502 Controller Installation a install guide, pp. 4, 15
| Relays | Four Form-C (dry) on LP1502 |
|---|---|
| Strike | NO and C poles |
| Maglock | NC and C poles |
| Diode current | 1x strike current |
| Diode voltage | 4x strike voltage |
| Typical diode | 1N4002 (100V/1A) for 12 or 24 V DC |
Common mistakes
From: Mercury LP1502 Controller Installation a install guide, p. 15
- Wiring a maglock to NO. The door then stays unlocked until a valid read and locks when the relay fires.
- Leaving out the diode. Lock feedback can cause premature relay failure and affect the controller's operation.
- Putting the protection circuit back at the panel on a long run. Keep it within 12 inches (30 cm) of the lock.
Source: HID Mercury MR52-S3B Reader Interface In install guide · p. 10
Applies to
LP1502 · PLT-05244 rev A.7MR52-S3B · PLT-06451
Sources
- Mercury LP1502 Controller Installation and Specifications, p. 15 (PLT-05244 Rev A.7)
- Mercury LP1502 Controller Installation and Specifications, p. 4 (PLT-05244 Rev A.7)
- HID Mercury MR52-S3B Reader Interface Installation and Specifications, p. 10 (PLT-06451 Rev A.1)