How do I find a ground fault or missing SLC devices on a Silent Knight 6820 fire panel
A GROUND FAULT on the Silent Knight 6820 means the panel senses current flowing from one or more terminals to earth (Terminal 2). Find it by removing wiring connections one at a time, waiting at least five seconds after each, until the fault clears; the last wire you pulled is on the faulted circuit. If a computer is connected by serial or USB cable the panel also shows a ground fault, which clears when you unplug it.
Steps
From: 6820/6820EVS Addressable Fire Alarm Cont manual, pp. 149-150
- Confirm it is a real faultIf a computer is connected to the 9-pin serial connector or USB, the panel goes into ground fault. Disconnect the computer; that trouble clears on its own.
- Remove one field wiring connection at a timeTake off one circuit's wiring, then pause at least five seconds before removing the next one.
- Watch for the trouble to clearWhen the GROUND FAULT message goes away, the last circuit you removed is the one touching earth. Reconnect the others.
- Walk the faulted circuitAnd look for a conductor or shield touching a box, conduit or structure, then repair it and reconnect.
- For devices showing Missing, check addressing and polarityMake sure no address is used twice (that shows DBL ADDR), contact monitor DIP switches were set before power was applied, and SLC polarity is correct.
- Measure SLC loop impedanceDisconnect both SLC wires at the panel and measure positive to negative and negative to positive: both must be greater than 500 k ohms. Then short positive to negative at the far end and measure again: both must be less than 50 ohms.
- Use the SLC device locaterTo find a device: Main Menu, 2 for Point Functions, 4 for SLC Single Device Locater, pick the loop and enter the address. The device LED flashes. The system shuts down while locating and resumes when you exit.
Specs & limits
From: 6820/6820EVS Addressable Fire Alarm Cont manual, pp. 139, 149
| Earth terminal | Terminal 2 |
|---|---|
| Wait between wires | At least five seconds |
| SLC open test | Greater than 500 k ohms both ways |
| SLC loop test | Less than 50 ohms both ways with the far end shorted |
| Contact ID code | Ground fault trouble reports 310 |
| Module supply | 27.2-27.4V at the 6815 or 5815XL terminals with AC present |
Common mistakes
From: 6820/6820EVS Addressable Fire Alarm Cont manual, p. 149
- Chasing a ground fault while a laptop is plugged in. The serial or USB connection itself causes the fault on this panel.
- Connecting SLC devices to the SLC IN terminals of a 6815 or 5815XL. Devices go on the SLC OUT terminals.
- Testing a T-tapped SLC as one loop. Test each T-tap individually.
Applies to
6820 · Manual LS10144-001SK-E6820EVS
Sources
- 6820/6820EVS Addressable Fire Alarm Control Panel Manual, p. 149 (LS10144-001SK-E Rev E)
- 6820/6820EVS Addressable Fire Alarm Control Panel Manual, p. 150 (LS10144-001SK-E Rev E)