How do I program the bell cutoff time on a dmp xr150
Set Bell Cutoff on the DMP XR150 in Bell Options so the Panel Bell and Bell Output run 1–99 minutes, or continuously.
Steps
From: DMP XR150, XR550 Programming guide: XR15 programming guide, pp. 51, 56, 66, 69
- In Bell Options, at
BELL CUTOFF, enter how long the Panel Bell and Bell Output stay on - Enter 1 to 99 minutes, or 0 for continuous bell output
- For Cancel Verify on an All/Perimeter or Home/Sleep/Away system, set Bell Cutoff Time greater than 0
Specs & limits
From: DMP XR150, XR550 Programming guide: XR15 programming guide, pp. 51, 56, 66, 69
| Note | Default is 15 minutes. |
|---|---|
| Note | Disarming the area resets the cutoff time. |
| Note | Fire Bell Output turns off when Bell Cutoff time expires. |
| Note | Burglary Bell Output duration follows Bell Cutoff Time. |
| Note | A DMP 1135 wireless siren follows panel bell cadence and bell cutoff time up to 15 minutes. |
Applies to
XR550
Sources
- DMP XR150, XR550 Programming guide: XR150/XR550 Series Programming Guide (LT-1232), p. 51, p. 51
- DMP XR150, XR550 Programming guide: XR150/XR550 Series Programming Guide (LT-1232), p. 69, p. 69
- DMP XR150, XR550 Programming guide: XR150/XR550 Series Programming Guide (LT-1232), p. 66, p. 66
- DMP XR150, XR550 Programming guide: XR150/XR550 Series Programming Guide (LT-1232), p. 56, p. 56