How to program wireless zone on dmp XR550
Program an XR550 wireless zone by selecting YES at WIRELESS? and entering the device serial number on a valid wireless zone.
Steps
From: DMP XR150, XR550 Programming guide: XR15 programming guide, pp. 71, 73
- Program the wireless House Code in System Options before adding DMP wireless zones
- At NEXT ZONE, select NO so WIRELESS?NO YES displays.
- Select YES to program the zone as a DMP wireless zone
- Use a zone number from 500 through 999 for 1100 Series Wireless, or 400 to 449 for a 1144 Series key fob
- At SERIAL#, enter the eight-digit serial number on the DMP wireless device
- For an 1100T Wireless Translator, select YES at COMP WLS? instead of programming it as a DMP wireless zone
- At COMP WLS SRL #, enter the eight-character serial, or select LRN and tamper the transmitter when TRANSMIT NOW appears
- For a 1144 key fob used as panic or holdup, set TWO BUTTON? to NO for 1-button panic or YES for 2-button panic
- For an 1122, 1126, or 1127 PIR, set SENSITIVITY to LOW or HIGH
- For an 1122, set PET IMMUNITY to YES or NO
- At NEXT ZONE, select YES to program another zone, or NO then press CMD to continue to Alarm Action
Specs & limits
From: DMP XR150, XR550 Programming guide: XR15 programming guide, pp. 71, 73
| XR550 1100 Series wireless zones | 500 through 999 |
|---|---|
| 1144 Series key fob zones | 400 to 449 |
| Note | WIRELESS? and COMP WLS? default is NO; House Code is required first |
| Note | Already In Use displays if that serial is already on another zone |
| Note | TWO BUTTON? default is NO |
| Note | PIR sensitivity default is LOW (75%); HIGH is maximum sensitivity |
| Note | 1122 pet immunity is for animals up to 55 pounds; default is NO |
Applies to
XR550