| Type | Line interactive |
|---|---|
| Power | (1) OVC II AC in: NEMA 5‑15P, 1.8 m (5.9 ft) non-removable power cord (4) Battery backup/surge protection: NEMA 5‑15R (4) Surge protection: NEMA 5‑15R (Outlets are not individually resettable) |
| Status | Off: device not turned on Flashing white: initializing / factory default Steady white: waiting for adoption Steady blue: device adoption and working Flashing blue: battery mode Alternating white/blue: firmware upgrading Rapid flashing blue: locate Steady red: warning Flashing red: low battery |
| Weight | 14 kg (30.9 lb) |
| Buttons | (1) Power (1) Factory reset |
| Runtime | Full load: 2.3 min Half load: 8 min |
| Capacity | 1,440VA/1,000W |
| Store SKU | UPS-2U-US |
| Wave Form | Simulated sine wave (Battery mode) |
| Dimensions | 442.4 x 300 x 87.4 mm (17.4 x 11.8 x 3.4") |
| Management | Ethernet |
| Form Factor | Rack mount (2U) |
| Battery Type | (2) Lead Acid 12V, 9Ah |
| Power Method | (1) TN system, 120V AC, 12A Max., 50/60 Hz |
| Transfer Time | 6 ms typical; 10 ms max. (Battery mode) |
| Certifications | FCC, IC, UL 1778, CSA C22.2 No. 107.3 |
| NDAA Compliant | True |
| Output Voltage | 120V AC |
| Frequency Range | AC mode: 50/60 Hz ±5 Hz (Auto sensing) Battery mode: 60 Hz ±1 Hz |
| Weatherproofing | IP20 |
| Enclosure Material | Galvanized steel |
| Operating Altitude | 3,000 m (1.9 mi) |
| Input Voltage Range | 89–145V AC |
| Networking Interface | (1) 100/10 MbE port for network connection (2) GbE ports for surge in/out |
| AC Voltage Regulation | ±10% (Battery mode) |
| Battery Charging Time | 6-8 hours recovery to 90% capacity |
| Nominal Input Voltage | 120V AC |
| Operating Environment | Pollution Degree 2 |
| Overload at Battery Mode | 110% shutdown in 5 sec 120% shutdown immediately |
| Overload at On-Line Mode | 110% 5 min go to fault 120% go to fault immediately |
| Ambient Operating Humidity | 0 to 95% noncondensing |
| Ambient Storage Temperature | -20 to 50° C (-4 to 122° F) |
| Output Short-Circuit Current | Ipeak 348.0A Irms 115.1A |
| Ambient Operating Temperature | 0 to 40° C (32 to 104° F) |
| Short Circuit Protection at On-Line Mode | Breaker, 250V AC, 15A |
Distribution partner
Distribution partner coming soon
From Techs
No tech listings for this part yet.
Wanted
No wanted posts yet.
Aliases and rough areas only. No exact locations.
Shop New
0 business listings mention this part.
Guides tagged with the UPS-2U, grouped by type
No Defaults guides for the UPS-2U yet. Suggest a guide
No Programming guides for the UPS-2U yet. Suggest a guide
No Troubleshooting guides for the UPS-2U yet. Suggest a guide
No other Ubiquiti panel guides for the UPS-2U yet. Suggest a guide
No discussions tagged to this part yet.
Be the first to add a field photo of this install.
Manufacturer photos are credited to the vendor. Field photos are real installs, reviewed before they are public, and credited to the uploader. Report a photo. We remove a reported photo within 24 hours.
Real installs only. EXIF and GPS are stripped. A moderator reviews the photo before it is public. An approved photo is credited to your alias.
Sign in to add a field photo.
Report a manufacturer or field photo that should come down.