LV Handbook › Parts › Ubiquiti › UniFi Power Tech › UPS-2U-Pro
Ubiquiti UPS-2U-Pro
1 / 1

Ubiquiti UPS-2U-Pro

Ubiquiti

Power · UPS 2U Pro

Documents & links

ups-2u-pro-us ups-2u-pro-us

Reviews

No reviews yet.

Where to Buy

Guides

Specs

TypeLine interactive
Power(1) OVC II AC in: NEMA 5‑20P (8) Battery backup/surge protection: NEMA 5‑20R (Outlets are individually resettable)
StatusOff: device not turned on Flashing white: initializing / factory default Steady white: waiting for adoption Steady blue: device adoption and working Flashing blue: battery mode Alternating white/blue: firmware upgrading Rapid flashing blue: locate Steady red: warning Flashing red: low battery
Weight32 kg (70.5 lb)
Buttons(1) Power (1) Factory reset (1) Circuit breaker
Display3.7” touchscreen
RuntimeFull load: 9 min Half load: 22 min
Capacity1920VA/1920W
EthernetTrue
Store SKUUPS-2U-Pro-US
Wave FormPure sine wave (Battery mode)
Dimensions442.4 x 87.4 x 630 mm (17.4 x 3.4 x 24.8")
ManagementEthernet
Form FactorRack mount (2U)
Mobile AppsiOS™: Version 10.36.1 and later Android™: Version 10.39.3 and later
Battery Type(1) Lead Acid 72V, 10Ah
Power Method(1) TN system, 120V AC, 16A Max., 50/60 Hz
Transfer Time6 ms typical; 10 ms max. (Battery mode)
UniFi NetworkVersion 10.5.67 and later
CertificationsFCC, IC, UL 1778, CSA C22.2 No. 107.3
NDAA CompliantTrue
Output Voltage120V AC
Frequency RangeAC mode: 50/60 Hz ±5 Hz (Auto sensing) Battery mode: 60 Hz ±1 Hz
WeatherproofingIP20
Enclosure MaterialGalvanized steel
Operating Altitude3,000 m (1.9 mi)
Input Voltage Range89–145V AC
Networking Interface(1) 100/10 MbE port for network connection (2) GbE ports for surge in/out
AC Voltage Regulation±1.5% (Battery mode)
Battery Charging Time8 hours recovery to 90% capacity
Nominal Input Voltage120V AC
Operating EnvironmentPollution Degree 2
Nominal Output Voltage120V AC
Overload at Battery Mode103–120% 1 min go to fault 120–150% 10 sec go to fault 150% 0.5 sec go to fault
Overload at On-Line Mode103–120% 5 min go to fault 120–150% 10 sec go to fault 150% 1 sec go to fault
Emergency Power Off (EPO)True
Ambient Operating Humidity0 to 95% noncondensing
Ambient Storage Temperature-15 to 50° C (5 to 122° F)
Ambient Operating Temperature0 to 40° C (32 to 104° F)
Short Circuit Protection at On-Line ModeBreaker, 250V AC, 20A

Discussions 0 tagged

No discussions tagged to this part yet.

Start a discussion about this part