HireLV Handbook › Wiring diagrams › Access control › HES › 9600

HES 9600 Electric Strike

Suggest a correction

Suggest a correction

A free account is required. Reports stay private until a correction is published.

9600 Electric Strike

12 VDC plug 24 VDC plug 12 VDC, no connector 24 VDC, no connector Latchbolt monitor Latchbolt strike monitor
HES 9600HES 9600 12 VDC plug. Red connects to + supply (12 V: join with Violet; 24 V: alone). Violet connects to 12 V: join with Red to +; 24 V: join with Black. Black connects to 12 V: join with Red/green to −; 24 V: join with Violet. Red/green connects to − supply. White / Orange / Green connects to Latchbolt monitor C / NO / NC. Brown / Blue / Yellow connects to Latchbolt strike monitor C / NO / NC.HES 960012 VDC plugSolenoidRed+ supply (12 V: join with Vio…Violet12 V: join with Red to +; 24…Black12 V: join with Red/green to…Red/green− supplyLBM optionWhite / Orange / GreenLatchbolt monitor C / NO / NCLBSM optionBrown / Blue / YellowLatchbolt strike monitor C /…
HES 9600 12 VDC plug. Red connects to + supply (12 V: join with Violet; 24 V: alone). Violet connects to 12 V: join with Red to +; 24 V: join with Black. Black connects to 12 V: join with Red/green to −; 24 V: join with Violet. Red/green connects to − supply. White / Orange / Green connects to Latchbolt monitor C / NO / NC. Brown / Blue / Yellow connects to Latchbolt strike monitor C / NO / NC.

Terminals Flag

TerminalGroupFunctionConnects to
Red Solenoid + supply (12 V: join with Violet; 24 V: alone) Flag
Violet Solenoid 12 V: join with Red to +; 24 V: join with Black Flag
Black Solenoid 12 V: join with Red/green to −; 24 V: join with Violet Flag
Red/green Solenoid − supply Flag
White / Orange / Green LBM option Latchbolt monitor C / NO / NC Flag
Brown / Blue / Yellow LBSM option Latchbolt strike monitor C / NO / NC Flag

Key specs

Voltage12 or 24 VDC continuous duty
Current500 mA @12 V, 250 mA @24 V
Resistance24 Ω @12 V, 96 Ω @24 V
Tolerance±10%
Wire gauge12 V: 18 ga ≤200 ft, 16 ga 200–400 ft; 24 V: 22 ga ≤300 ft, 20 ga 300–400 ft (round trip)
UL 10341500 lb static, 70 ft-lb dynamic, 250,000 cycles

Verify input voltage with a meter first; >10% over rating can damage the solenoid

Fail safe negates the fire rating; don't use fail safe in fire-rated or windstorm applications

Switch states listed for an unpowered strike with the monitor unactuated (door open)

When converting LBSM to fail safe, move the monitoring switch position too

How to wire it

  1. Connect Red to + supply (12 V: join with Violet; 24 V: alone).
  2. Connect Violet to 12 V: join with Red to +; 24 V: join with Black.
  3. Connect Black to 12 V: join with Red/green to −; 24 V: join with Violet.
  4. Connect Red/green to − supply.
  5. Connect White / Orange / Green to Latchbolt monitor C / NO / NC.
  6. Connect Brown / Blue / Yellow to Latchbolt strike monitor C / NO / NC.

Source

9400|9500|9600|9700|9800 Electric Strike Installation Instructions & Frame Preparation · AADSS1053638 rev © 2024 (PDF Apr 2024)

Values from AADSS1053638 rev © 2024 (PDF Apr 2024).

Verify against the manufacturer's install guide.

Open in builder Program it in OnGuard

Shop this part