HireLV Handbook › Software › OnGuard › How to add a door in Lenel OnGuard
LenelS2 OnGuard 7.x · 8.x Software setup ~20 min

How to add a door in Lenel OnGuard

Suggest a correction

Suggest a correction

A free account is required. Reports stay private until a correction is published.

LP1502 controller, MR52 interface, OSDP readers, REX and strike. Values come from your wiring diagram.

The steps are the same in 7.x and 8.x. 8.3 adds Mercury M-Series and IP client connections. Fields marked Verify in your version were not confirmed in public docs.

1. Add the access panel Flag

System Administration › Access Control › Access Panels

Pick the panel type for the controller, click Add, then fill the Location tab. Lenel names Mercury boards with LNL part numbers: LP1502 = LNL-X2220, EP1502 = LNL-2220.

FieldSet to
Panel type LNL-X2220 (Mercury LP1502)
Name Lobby controller
Online Checked
Primary connection IP address of the LP1502
Downstream port baud 38,400 (match the MR52 switches) Verify in your version

2. Add Reader 1 on the MR52 Flag

Access Control › Readers and Doors › Add

In OnGuard the MR52 is not its own object. It is the reader Type LNL-1320. Both readers share one address and differ by Reader Number.

FieldSet to
Name Lobby — Entry
Panel Lobby controller
Type LNL-1320 (Dual Interface) = MR52
Port / Address / Reader Number Port 2 · Address 0 · Reader 1
Output OSDP Verify in your version
Card format Site format, for example 26-bit

3. Set OSDP, keypad and door timing Flag

Readers and Doors › reader settings

Turn on Secure Channel only if the reader is set for it. Strike time and held-open time are in seconds.

FieldSet to
OSDP address 0
Secure Channel Off for the first test, then On Verify in your version
Keypad None when the reader has no keypad
Strike time 5 s
Strike mode Fail-secure

4. Add Reader 2 Flag

Readers and Doors › Add

Same MR52 address, Reader Number 2. Pair it with Reader 1 so both readers control one door.

FieldSet to
Name Lobby — Exit
Port / Address / Reader Number Port 2 · Address 0 · Reader 2
OSDP address 0
Paired reader Paired with Reader 1 Verify in your version

5. Check door contact, REX and strike Flag

Readers and Doors › inputs and outputs

Map the door contact, REX and strike to the terminals in the diagram.

FieldSet to
Door contact MR52 input · NC
REX MR52 input
Strike relay MR52 relay · fail-secure

6. Timezone and access level Flag

Access Control › Timezones, then Access Levels

Make or reuse a timezone, then an access level that includes the new readers. Assign it to a test badge.

FieldSet to
Timezone Always, or business hours
Access level Lobby — All hours
Readers in the level Entry and exit readers

7. Download and test in Alarm Monitoring Flag

Alarm Monitoring › System Status

Download the panel, then use Open Door(s) to fire the strike. Present a badge, press the REX, and hold the door past the held-open time.

FieldSet to
Expect Access granted on the readers
Expect REX releases the strike

Questions

How do you add an MR52 in OnGuard?

The MR52 is the reader Type LNL-1320 on Readers and Doors, not a separate device. LP1502 is LNL-X2220 and EP1502 is LNL-2220.

Why will a Mercury-branded board not come online?

Mercury-branded boards can be blocked by the OnGuard license OEM mask. OnGuard expects LNL-branded boards.

Planning aid only. Values are typical and vary by manufacturer, code edition and jurisdiction. Verify with manufacturer data, NEC/NFPA/TIA and the local AHJ. HireLV is not liable for designs based on these tools.