D9127T/U POPIT Module
Flag notes: Sensor loop limit conflict: datasheet <100 Ω vs install guide 1000 Ω · D9210 not mentioned in docs · Full DIP table not transcribed (2 rows only)
| Terminal | Group | Function | Connects to | |
|---|---|---|---|---|
| DATA − ×2 | Data loop | POPEX loop −, in/out | Flag | |
| DATA + ×2 | Data loop | POPEX loop +, in/out | Flag | |
| LOOP − | Sensor loop | Detector loop return | Flag | |
| LOOP + | Sensor loop | Detector loop, 33 kΩ EOL at farthest point | Flag | |
| DIP 0–6 | Switch | Point address | Flag | |
| Reed | D9127T only | Cover tamper | Flag |
| Power | 12 VDC nominal, 0.8 mA max |
|---|---|
| Eol | 33 kΩ (included) |
| Popex to popit | 90 Ω max |
| Terminal wire | 12 AWG solid max / 22 AWG stranded min |
| Data loop length | 1800 ft@22, 2890@20, 4600@18, 7320@16, 11650@14 AWG (all loops combined) |
Metal enclosure required for UL Intrusion/NFPA/ULC
Twisted pair 6 twists/ft for data and sensor loops
Solid wire recommended
D9127U/T POPIT Module Quick Installation Guide · (c) 2024 Bosch Security Systems B.V. rev 2024
Values from (c) 2024 Bosch Security Systems B.V. rev 2024.
Verify against the manufacturer's install guide.
Planning aid only. Values are typical and vary by manufacturer, code edition and jurisdiction. Verify with manufacturer data, NEC/NFPA/TIA and the local AHJ. HireLV is not liable for designs based on these tools.