DMP 734 Wiegand Interface Module
Suggest a correction
734 Wiegand Interface Module
Flag notes: Guide contains a conflicting 'do not connect' line for KYPD OUT at 24 V
DMP 734 DMP 734 Wiegand reader. 1 RED connects to 12/24 VDC reader power out. 2 WHT connects to Data 1. 3 GRN connects to Data 0. 4 BLK connects to Ground. 5 LC connects to Switched-ground LED control. 6 RA connects to Switched-ground indicator. 7 AS connects to Switched-ground indicator. 8 Z1 connects to Zone 1 (burglary), grounded. 9 GND connects to Ground Z1/Z2. 10 Z2 connects to Zone 2 door contact / bypass. 11 Z3 connects to Zone 3 REX. 12 GND connects to Ground Z3. 13 Z4+ connects to Zone 4 Class B (fire-capable) +. 14 Z4− connects to Zone 4 −. NO / C / NC connects to Door strike relay 10 A @ 12/24 VDC. KYPD IN / KYPD OUT connects to Keypad bus to panel / next device. DMP 734 Wiegand reader Reader 1 RED 12/24 VDC reader power out 2 WHT Data 1 3 GRN Data 0 4 BLK Ground Indicator 5 LC Switched-ground LED control 6 RA Switched-ground indicator 7 AS Switched-ground indicator Zone 8 Z1 Zone 1 (burglary), grounded 9 GND Ground Z1/Z2 10 Z2 Zone 2 door contact / bypass 11 Z3 Zone 3 REX 12 GND Ground Z3 13 Z4+ Zone 4 Class B (fire-capable)… 14 Z4− Zone 4 − Relay NO / C / NC Door strike relay 10 A @ 12/2… Bus KYPD IN / KYPD OUT Keypad bus to panel / next de…
DMP 734 Wiegand reader. 1 RED connects to 12/24 VDC reader power out. 2 WHT connects to Data 1. 3 GRN connects to Data 0. 4 BLK connects to Ground. 5 LC connects to Switched-ground LED control. 6 RA connects to Switched-ground indicator. 7 AS connects to Switched-ground indicator. 8 Z1 connects to Zone 1 (burglary), grounded. 9 GND connects to Ground Z1/Z2. 10 Z2 connects to Zone 2 door contact / bypass. 11 Z3 connects to Zone 3 REX. 12 GND connects to Ground Z3. 13 Z4+ connects to Zone 4 Class B (fire-capable) +. 14 Z4− connects to Zone 4 −. NO / C / NC connects to Door strike relay 10 A @ 12/24 VDC. KYPD IN / KYPD OUT connects to Keypad bus to panel / next device.
Terminals Flag
Terminal Group Function Connects to
1 RED
Reader
12/24 VDC reader power out
Flag
2 WHT
Reader
Data 1
Flag
3 GRN
Reader
Data 0
Flag
4 BLK
Reader
Ground
Flag
5 LC
Indicator
Switched-ground LED control
Flag
6 RA
Indicator
Switched-ground indicator
Flag
7 AS
Indicator
Switched-ground indicator
Flag
8 Z1
Zone
Zone 1 (burglary), grounded
Flag
9 GND
Zone
Ground Z1/Z2
Flag
10 Z2
Zone
Zone 2 door contact / bypass
Flag
11 Z3
Zone
Zone 3 REX
Flag
12 GND
Zone
Ground Z3
Flag
13 Z4+
Zone
Zone 4 Class B (fire-capable) +
Flag
14 Z4−
Zone
Zone 4 −
Flag
NO / C / NC
Relay
Door strike relay 10 A @ 12/24 VDC
Flag
KYPD IN / KYPD OUT
Bus
Keypad bus to panel / next device
Flag
Key specs
Power 12/24 VDC
Relay 10 A @ 12/24 VDC, 35 mA draw
Zone output 750 mA max total
Eol DMP 311 1 kΩ
Bus devices XR150: 8, XR550: 16
Osdp firmware 106+, hardware 102+
Install 333 suppressor across C and the used contact
At 24 V only another 24 V 734 may connect to KYPD OUT
How to wire it
Connect 1 RED to 12/24 VDC reader power out. Connect 2 WHT to Data 1. Connect 3 GRN to Data 0. Connect 4 BLK to Ground. Connect 5 LC to Switched-ground LED control. Connect 6 RA to Switched-ground indicator. Connect 7 AS to Switched-ground indicator. Connect 8 Z1 to Zone 1 (burglary), grounded. Connect 9 GND to Ground Z1/Z2. Connect 10 Z2 to Zone 2 door contact / bypass. Connect 11 Z3 to Zone 3 REX. Connect 12 GND to Ground Z3. Connect 13 Z4+ to Zone 4 Class B (fire-capable) +. Connect 14 Z4− to Zone 4 −. Connect NO / C / NC to Door strike relay 10 A @ 12/24 VDC. Connect KYPD IN / KYPD OUT to Keypad bus to panel / next device.
Source
734 Wiegand Interface Module Installation Guide
· LT-0737
rev 1.07 (© 2026)
Values from LT-0737 rev 1.07 (© 2026).
Verify against the manufacturer's install guide.