MR16out-S3 Output Processor

Mercury MR16out-S3Mercury MR16out-S3 Wiring diagram.Mercury MR16out-S3MR16out-S3 Output ProcessorMR16out-S3TerminalsT1Source → MR16out-S3 → Field deviceSource+ −MR16out-S3T1T2Field devicefield wiring

Address / baud

address 0–31 (binary). S1–S5 are the address, S6–S7 the baud, S8 encryption.

Address 5
Baud 38400

S1 + S3 ON = address 5 · S6 + S7 ON = 38,400 bps

S7S6Baud
OFFOFF115200
OFFON9600
ONOFF19200
ONON38400

S8: encryption required (undefined before fw 1.38.1)

Termination jumper J1 is not on the DIP bank. Install it on the first and last unit only.

How to wire it

  1. Follow the Mercury MR16out-S3 install guide.

Source

Mercury MR16out-S3 Processor Installation and Specifications · PLT-05251 rev A.4

Values from PLT-05251 rev A.4.