Flag notes: Guide text says SIO RS-485 on TB10; board drawing shows RS-485 on TB6 and relays on TB10. Data follows the drawing.
Mercury MR52 Mercury MR52 Osdp reader. TB7 VIN, VOUT, GND connects to 12–24 VDC ±10% in; VOUT = VIN pass-through. TB6 TR+, TR−, GND connects to 2-wire to Mercury controller; two NC positions unused. TB1–TB4 IN1–IN8 connects to Two terminals per input; unsupervised or 1k/1k 1% supervised. TB5 TMP, GND connects to Cabinet tamper, NC, no EOL; jumper if unused. TB5 PFL, GND connects to Power fault, NC, no EOL; jumper if unused. TB8 VO, LED, BZR, D1/CLK/TR+, D0/DAT/TR−, GND connects to TTL D1/D0 or Clock/Data, F/2F, or 2-wire RS-485 OSDP. TB9 VO, LED, BZR, D1/CLK/TR+, D0/DAT/TR−, GND connects to Same as reader 1. TB10 RLY1–RLY2 NO, C, NC connects to Form C, NO 5 A / NC 3 A @ 30 VDC. TB11 RLY3–RLY4 NO, C, NC connects to Form C. TB12 RLY5–RLY6 NO, C, NC connects to Form C. J4 connects to RS-485 termination; end units only. J1 connects to Reader power: 12V (needs VIN >20 VDC) or PT pass-through. Mercury MR52 Osdp reader Power TB7 VIN, VOUT, GND 12–24 VDC ±10% in; VOUT = VIN… RS-485 (SIO) TB6 TR+, TR−, GND 2-wire to Mercury controller;… Inputs TB1–TB4 IN1–IN8 Two terminals per input; unsu… TB5 TMP, GND Cabinet tamper, NC, no EOL; j… TB5 PFL, GND Power fault, NC, no EOL; jump… Reader 1 TB8 VO, LED, BZR, D1/CLK/… TTL D1/D0 or Clock/Data, F/2F… Reader 2 TB9 VO, LED, BZR, D1/CLK/… Same as reader 1 Relays TB10 RLY1–RLY2 NO, C, NC Form C, NO 5 A / NC 3 A @ 30… TB11 RLY3–RLY4 NO, C, NC Form C TB12 RLY5–RLY6 NO, C, NC Form C Jumper J4 RS-485 termination; end units… J1 Reader power: 12V (needs VIN…
Mercury MR52 Osdp reader. TB7 VIN, VOUT, GND connects to 12–24 VDC ±10% in; VOUT = VIN pass-through. TB6 TR+, TR−, GND connects to 2-wire to Mercury controller; two NC positions unused. TB1–TB4 IN1–IN8 connects to Two terminals per input; unsupervised or 1k/1k 1% supervised. TB5 TMP, GND connects to Cabinet tamper, NC, no EOL; jumper if unused. TB5 PFL, GND connects to Power fault, NC, no EOL; jumper if unused. TB8 VO, LED, BZR, D1/CLK/TR+, D0/DAT/TR−, GND connects to TTL D1/D0 or Clock/Data, F/2F, or 2-wire RS-485 OSDP. TB9 VO, LED, BZR, D1/CLK/TR+, D0/DAT/TR−, GND connects to Same as reader 1. TB10 RLY1–RLY2 NO, C, NC connects to Form C, NO 5 A / NC 3 A @ 30 VDC. TB11 RLY3–RLY4 NO, C, NC connects to Form C. TB12 RLY5–RLY6 NO, C, NC connects to Form C. J4 connects to RS-485 termination; end units only. J1 connects to Reader power: 12V (needs VIN >20 VDC) or PT pass-through.
Terminals Flag
Terminal Group Function Connects to
TB7 VIN, VOUT, GND
Power
12–24 VDC ±10% in; VOUT = VIN pass-through
Flag
TB6 TR+, TR−, GND
RS-485 (SIO)
2-wire to Mercury controller; two NC positions unused
Flag
TB1–TB4 IN1–IN8
Inputs
Two terminals per input; unsupervised or 1k/1k 1% supervised
Flag
TB5 TMP, GND
Inputs
Cabinet tamper, NC, no EOL; jumper if unused
Flag
TB5 PFL, GND
Inputs
Power fault, NC, no EOL; jumper if unused
Flag
TB8 VO, LED, BZR, D1/CLK/TR+, D0/DAT/TR−, GND
Reader 1
TTL D1/D0 or Clock/Data, F/2F, or 2-wire RS-485 OSDP
Flag
TB9 VO, LED, BZR, D1/CLK/TR+, D0/DAT/TR−, GND
Reader 2
Same as reader 1
Flag
TB10 RLY1–RLY2 NO, C, NC
Relays
Form C, NO 5 A / NC 3 A @ 30 VDC
Flag
TB11 RLY3–RLY4 NO, C, NC
Relays
Form C
Flag
TB12 RLY5–RLY6 NO, C, NC
Relays
Form C
Flag
J4
Jumper
RS-485 termination; end units only
Flag
J1
Jumper
Reader power: 12V (needs VIN >20 VDC) or PT pass-through
Flag
Key specs
Power 12–24 VDC ±10%, 550 mA max excluding readers
Power wire 18 AWG min
Sio 2-wire RS-485, 4,000 ft, 24 AWG shielded twisted pair, 120 Ω
Reader power 300 mA max per port
Reader cable TTL 6-cond 18 AWG 500 ft; F/2F 4-cond 18 AWG 500 ft; RS-485 24 AWG shielded 2,000 ft
Inputs 8 + tamper + power fault; 1k/1k 1% EOL; 30 Ω max loop
Relays 6 Form C; NO 5 A @ 30 VDC, NC 3 A @ 30 VDC
Dimensions 6 x 8 x 1 in
Temp 0–70 °C
12 VDC board power: J1 must be on PT
Contact protection diode (1N4002 typical) within 12 in of inductive loads
OSDP >200 ft or EMI: 120 Ω across RS-485 ends
Board earth ground connections required
How to wire it
Connect TB7 VIN, VOUT, GND to 12–24 VDC ±10% in; VOUT = VIN pass-through. Connect TB6 TR+, TR−, GND to 2-wire to Mercury controller; two NC positions unused. Connect TB1–TB4 IN1–IN8 to Two terminals per input; unsupervised or 1k/1k 1% supervised. Connect TB5 TMP, GND to Cabinet tamper, NC, no EOL; jumper if unused. Connect TB5 PFL, GND to Power fault, NC, no EOL; jumper if unused. Connect TB8 VO, LED, BZR, D1/CLK/TR+, D0/DAT/TR−, GND to TTL D1/D0 or Clock/Data, F/2F, or 2-wire RS-485 OSDP. Connect TB9 VO, LED, BZR, D1/CLK/TR+, D0/DAT/TR−, GND to Same as reader 1. Connect TB10 RLY1–RLY2 NO, C, NC to Form C, NO 5 A / NC 3 A @ 30 VDC. Connect TB11 RLY3–RLY4 NO, C, NC to Form C. Connect TB12 RLY5–RLY6 NO, C, NC to Form C. Connect J4 to RS-485 termination; end units only. Connect J1 to Reader power: 12V (needs VIN >20 VDC) or PT pass-through.
Source
Mercury MR52-S3 Reader Interface Installation and Specifications
· PLT-05248
rev A.5 (Sep 2024)
Values from PLT-05248 rev A.5 (Sep 2024).
Verify against the manufacturer's install guide.
Open in builder
Program it in OnGuard
Save
Download SVG
Export PDF
Related parts
Planning aid only. Values are typical and vary by manufacturer, code edition and jurisdiction. Verify with manufacturer data, NEC/NFPA/TIA and the local AHJ. HireLV is not liable for designs based on these tools.